Add to Cart
S4 intermittent duty rate quarter turn actuator with 1200 times/hour operation
Description
DCL modulating type electric actuators are S4 intermittent periodic duty operation. Actuator sequential, identical starts, runs and rests cycles with rated load. As the starting current affects temperature rise, if motor is not proper designed, actuator will be easily shut down during high frequently starts by thermal overheat protector in motor and actuator body will be very hot.
Actuators have been rigorous tested by CSA and certified per UL and CSA standard. In chemical and food & beverage industry, the fluid needs to be controlled very precisely, so the actuator start frequency is very high. 1200 times/hour can reach world leading level and can meet requirements of above industries.
Type | DCL-05E | DCL-10E | DCL-20E | DCL-40E | DCL-60E | DCL-100E | DCL-160E | DCL-250E |
Power | AC24/110/220 | AC24/110/220 | AC24/110/220 | AC24/110/220 | AC24/110/220 | AC110/220 | AC110/220 | AC110/220 |
Output Torque | 50Nm | 100Nm | 200Nm | 400Nm | 600Nm | 1000Nm | 1600Nm | 2500Nm |
Acting Time | 20S | 30S | 30S | 30S | 45S | 30S | 48S | 75S |
Turning Angle | 0-90° | 0-90° | 0-90° | 0-90° | 0-90° | 0-90° | 0-90° | 0-90° |
Motor Power | 10W | 25W | 40W | 90W | 90W | 120W | 140W | 140W |
Rated Current | 1.50/0.24/ 0.16A | 2.12/0.57/ 0.35A | 3.65/0.65/ 0.37A | 6.80/1.12/ 0.57A | 6.80/1.18/ 0.60A | 1.93/0.94A | 1.75/0.96A | 1.75/0.98A |
Total Weight | 2.5kg | 4.5kg | 9kg | 9.5kg | 10kg | 19kg | 19.5kg | 20kg |
Input Signal | 4-20mADC,1-5VDC,2-10VDC | |||||||
Output Singal | 4-20mADC | |||||||
Basic Error | not more than ±1% | |||||||
Reciprocating Error | not more than 1% | |||||||
Dead Space | 0.5%-5.0% adjustable | |||||||
Damping Characteristic | 0 times | |||||||
Repeating Error in Actuator | ≤1% | |||||||
Insulating Resistance | AC24V:100MΩ/250VDC AC110/220V:100MΩ/500VDC | |||||||
Withstand Voltage Class | AC24V:500VAC 1minute AC110/220V:1500VAC 1minute | |||||||
Protection Class | IP67 | |||||||
Installation Angle | 360°at any angle | |||||||
Electric Interface | Two G1/2 Wate-proof Cable Connectors,one for power line and one for signal line | |||||||
Ambient Temperature | -20℃~+55℃ | |||||||
Optional Function | Over-torque protector/Dehumidify Heater/Passive contact switch/Dome indicator/Handle | |||||||
Remark | Any other input or output signal needed, please specified in purchase order. |