Add to Cart
DCL modulating actuators feature advanced built-in self-diagnosis capabilities: in the event of power faults, position sensor failures, broken potentiometer, motor stall, etc., the control module will flash the indicator LED in different patterns and automatically cut off motor power to protect the system.
These actuators are stringently tested and CSA certified under both UL and CSA standards. They can endure up to 1,200 starts per hour and a total of over 200,000 starts at rated torque over the full life cycle.
| Type | DCL-05E | DCL-10E | DCL-20E | DCL-40E | DCL-60E | DCL-100E | DCL-160E | DCL-250E |
|---|---|---|---|---|---|---|---|---|
| Power | AC24/110/220 | AC24/110/220 | AC24/110/220 | AC24/110/220 | AC24/110/220 | AC110/220 | AC110/220 | AC110/220 |
| Output Torque | 50Nm | 100Nm | 200Nm | 400Nm | 600Nm | 1000Nm | 1600Nm | 2500Nm |
| Acting Time | 20S | 30S | 30S | 30S | 45S | 30S | 48S | 75S |
| Turning Angle | 0-90° | 0-90° | 0-90° | 0-90° | 0-90° | 0-90° | 0-90° | 0-90° |
| Motor Power | 10W | 25W | 40W | 90W | 90W | 120W | 140W | 140W |
| Rated Current | 1.50/0.24/ 0.16A | 2.12/0.57/ 0.35A | 3.65/0.65/ 0.37A | 6.80/1.12/ 0.57A | 6.80/1.18/ 0.60A | 1.93/0.94A | 1.75/0.96A | 1.75/0.98A |
| Total Weight | 2.5kg | 4.5kg | 9kg | 9.5kg | 10kg | 19kg | 19.5kg | 20kg |
| Input Signal | 4-20mADC,1-5VDC,2-10VDC | |||||||
| Output Singal | 4-20mADC | |||||||
| Basic Error | not more than ±1% | |||||||
| Reciprocating Error | not more than 1% | |||||||
| Dead Space | 0.5%-5.0% adjustable | |||||||
| Damping Characteristic | 0 times | |||||||
| Repeating Error in Actuator | ≤1% | |||||||
| Insulating Resistance | AC24V:100MΩ/250VDC AC110/220V:100MΩ/500VDC | |||||||
| Withstand Voltage Class | AC24V:500VAC 1minute AC110/220V:1500VAC 1minute | |||||||
| Protection Class | IP67 | |||||||
| Installation Angle | 360°at any angle | |||||||
| Electric Interface | Two G1/2 Wate-proof Cable Connectors,one for power line and one for signal line | |||||||
| Ambient Temperature | -20℃~+55℃ | |||||||
| Optional Function | Over-torque protector/Dehumidify Heater/Passive contact switch/Dome indicator/Handle | |||||||
| Remark | Any other input or output signal needed, please specified in purchase order. | |||||||